Products >> DC Inverter series >> 

  • OT-06W/DC
OT-06W/DC

OT-06W/DC

Product description:
1.Automatically adjust outlet water temp. upon the outdoor ambient temp.

2.Automatically adjust heating or cooling mode upon the outdoor ambient temp or indoor signal.
3.Modbus communication available.
4.Wifi operation available

Parameter:
Model   OT-05W/DC
Power Source V/Hz/Ph 220-240/50/1
Refrigerant   R410a/R290
Max. Heating Capacity (1) kW 20
C.O.P (1) W/W 4.72
Heating Capacity Min./Max.(1) kW 9.1 19.8
Heating Power Input Min./Max.(1) kW 1.54 4.2
C.O.P Min./Max. (1) W/W 4.76 5.95
Max. Heating Capacity (2) kW 19.3
C.O.P (2) W/W 3.86
Heating Capacity Min./Max.(2) kW 8.8 19.1
Heating power input Min./Max.(2) kW 1.9 5.1
C.O.P Min./Max. (2) W/W 3.8 4.51
Max. Cooling Capacity (3) kW 18
E.E.R (3) W/W 3.7
Cooling Capacity Min./Max.(3) kW 8.39 18.24
Cooling Power Input Min./Max.(3) kW 1.9 5.8
E.E.R Min./Max. (3) W/W 3.15 4.42
Max. Cooling Capacity (4) kW 14.5
E.E.R (4) W/W 2.81
Cooling Capacity Min./Max.(4) kW 6.62 14.4
Cooling Power Input Min./Max.(4) kW 1.7 5.4
E.E.R Min./Max. (4) W/W 2.68 3.89
Rated Current  A 21
Max Current A 30
Compressor Type   Twin Rotary 
Fan Quantity   2
Airflow m3/h 5000
Rated power W 200
Condenser Type   Plate Heat Exchanger
Pressure Drop kPa 25
Piping Connection Inch G1"
Noise Level   dB(A) 60
Net Dimension(L×D×H) mm 1060*455*1400
Net Weight Kg 120
(1) Heating condition: water inlet/outlet temperature: 30/35, Ambient temperature: DB 7/WB 6;
(2) Heating condition: water inlet/outlet temperature: 40/45, Ambient temperature: DB 7/WB 6;
(3) Cooling condition: water inlet/outlet temperature: 23/18, Ambient temperature: DB35/WB24;
(4) Cooling condition: water inlet/outlet temperature: 12/7, Ambient temperature: DB35/WB24.

Next Product:OT-05W/DC
WechatClose